Troubleshooting
Chiller High Pressure Alarm
A high pressure trip is a heat rejection problem. Where to look before resetting anything.
High pressure means the chiller cannot get rid of heat fast enough. The trip is protecting the compressor, so resetting it without finding the cause simply repeats the cycle. In Cape Town's dusty conditions the answer is usually at the condenser.
Work through airflow, then water flow, then charge. A blocked coil, a failed fan, a dirty strainer or air in the water circuit will all produce the same alarm, and each has a different fix.
Symptoms
What you are seeing.
- The chiller trips on high pressure after a short run
- Head pressure readings are high with a normal water temperature
- Condenser fans are not running or run at one speed only
- The condenser coil is visibly blocked with dust or debris
- The alarm repeats more often on hot afternoons
Likely causes
What usually causes it.
- A blocked or dirty condenser coil
- Restricted airflow from enclosure, recirculation or failed fans
- Low water flow from a blocked strainer or failing pump
- Overcharge or non-condensables in the refrigerant circuit
- A faulty high pressure switch or transducer
Before you call
What you can check yourself.
- Confirm the condenser fans are running
- Look through the coil for dust, leaves or building debris
- Check the pump is running and the strainer is clear
- Note the ambient temperature and time of day when the trip occurs
Questions
Asked most often.
Can I reset the chiller and keep running?
You can reset it, but if the cause is still there it will trip again, and repeated trips stress the compressor. Find the cause first.
Why does it only trip in summer?
Higher ambient temperature reduces the condenser's ability to reject heat. A coil that is marginal in winter will fail in February.
How often should the condenser be cleaned?
Quarterly for most units in this dust, more often if the chiller sits near a road, a kitchen extract or a building site.
Local versions
High pressure alarm in a specific suburb
The service behind this guide: ChillersEnquire
Still not right?
Send the details and we will confirm the next available visit. Enquiries are handled centrally at info@reyds.co.za.